At Arne Nielsen A/S we carry every boiler and every spare part in the Ferroli Atlas range – both the analogue Atlas and the digital Atlas D. Whether you need to replace a complete boiler or are missing a single part in the middle of a service, you get it all in one place.
Two versions: analogue and digital
Atlas comes with two types of control, so you can choose the one that suits the job and the customer:
- Atlas (analogue): classic thermostat control. Simple to operate and to service.
- Atlas D (digital): electronic control with display, adjustable parameters and fault codes that make troubleshooting faster.
| Series | Models | Control |
|---|---|---|
| Atlas | 32 · 47 · 62 · 78 · 95 | Analogue |
| Atlas D | 25 · 37 · 50 · 63 · 75 | Digital |
With ten models, the range covers everything from the family home to larger heating jobs in commercial and public buildings.
Common to the whole range
- Robust cast-iron block with 3-pass design for efficient heat transfer and a long service life.
- High-density rock wool insulation that keeps the heat in.
- For an external oil or gas burner, so boiler and burner can be matched to the job.
All spare parts for Atlas – also for older boilers
Many Atlas boilers have been running for years, and they need to be kept running. We stock spare parts for the whole range, including:
- Control boards, control panels and operating boards for Atlas D
- Operating, safety and hot water thermostats
- Sensors, pumps and expansion vessels
- Gaskets, draught regulators and wear parts
If you are missing a part you cannot find, write to us. We will find the right one.
Service tip: new control board in an Atlas D? Check P01
A new control board for Atlas D is supplied from the factory with parameter P01 = 1, which is the setting for an integrated Ferroli burner. If the boiler runs with an external burner, P01 must be set to 0. Otherwise the boiler locks out with fault A02.
- Press and hold the + and − keys for the hot water temperature at the same time for 10 seconds.
- The display shows P01.
- Change P01 to 0 with the − key.
- Exit the menu and reset the boiler.
Always check P01 before changing it. If it is already set to 0, the fault lies elsewhere.
One supplier for the whole Atlas range
Boilers for the replacement, spare parts for the service and expert advice on choosing model and burner – all at Arne Nielsen A/S.